Fueling Products

Fuel Management Systems

Other Solutions

Slideshow image

Power Sentinel™

The INCON Power Sentinel™ is a unique product that provides electrical power protection for all equipment at a site. It is easy to install, offers “whole store” versus “point-of-use” protection and provides a simple way to ensure power quality.

Features/Capabilities

Features

  • Reduces electricity demand and electrical noise.
  • Provides permanent, maintenance-free surge protection.
  • Offers “whole site” vs. “point-of-use” protection.
  • Easy to install and requires less down time than similar models.
  • Provides the most simple and costeffective way to ensure power quality.

Capabilities

Power Sentinel™ utilizes established technology in a unique manner to provide a site with power conditioning and surge protection capabilities.

  • Cost-effective and maintenance free package that provides surge and spike suppression, noise filtration and power factor correction.
  • Protects entire facility from costly power surges.
  • Helps equipment to run at optimal efficiency thereby reducing energy consumption.
  • Prevents business disruptions from electrical noise.
  • Creates cost savings by increasing up time and reducing equipment maintenance costs.
  • Easy installation at the electrical panel.
  • Achieves power factor correction which can lower demand charges and motor operating temperatures thereby prolonging the life of electrical equipment.

Applications

The Power Sentinel™ is connected in parallel into AC systems at the main power panel.

  • Available in single-phase and three-phase models.
  • Connected to the electrical power panel via conduit and a dedicated circuit breaker.
  • Maintenance-free, solid-state device with no moving parts.
  • No need to service during operating life.
  • NEMA 12-rated enclosure which makes it moisture, dust and tamper resistant.
  • Establishes power quality before it gets to the main breaker allowing the entire site to benefit from clean power.

Specifications


UNIT MODEL
PS-1C240
PS-3Y208
Power line voltage
120 v or 240 v
120 v or 208 v
Phase and confi guration
Single
3 Wye
Frequency (Hz)
50/60
50/60
Power Dissipation (J)
(2 £gs current wave)
1,270
3,300
Peak Pulse Current (A)
(8/20 £gs current wave)
40k - 120k
40k - 120k
Maximum Clamping (V)
(@ 200A, 8/20 μs current wave)
405/690
630
Total Capacitance (μF)
200
495
Operating temperature
-40° to 70° C
-40° to 158° F
-40° to 70° C
-40° to 158° F
Line wires (AWG)
10
10
Circuit breaker required (A)
20
40
Dimensions
10" x 8" x 6"
12" x 12" x 6"
Weight (lbs.)
17
28

Ordering Information


PART NUMBERDESCRIPTION
PS-1C240 120/240 VAC (single-phase)
PS-3Y208 208/240 VAC (three-phase)
PS-3Y480 277/480 VAC (three-phase)
PS-3D600 600 VAC (three-phase)

Note:

  • Power Sentinel™ is quickly installed and wired to the main power panel for power conditioning and surge protection.
  • The unit must agree with the voltage supply at the site (contact a licensed electrician for this information and for unit installation).