Fueling Products

Fuel Management Systems

Other Solutions

Slideshow image

TS-SCCM Secondary Containment Control Module

The secondary containment monitoring option of the TS-5 Series uses the siphon port of the submersible turbine pump to draw and maintain a vacuum on the secondary containments of lines, sumps, tanks and vapor lines. Using our Autolearn™ technology, the vacuum level is continuously monitored and compared to established leak rates to ensure that the secondary containment is tight. Up to four different containments can be connected to each STP using a combination of single and dual channel TS-SCCMs.

Data


Part Description
TS-SCCM/1 Single secondary containment control module
TS-SCCM/2 Double secondary containment control module
TS-SCMCAL Leak generator kit, one per station

Part Description
TSP-SCLSI Product, vapor line, sump containment install kit
TSP-SCTKI Tank containment install kit, in-tank hose sold separately

Notes:

  1. Available on the TS-5 Series fuel management systems and TS-EMS environmental monitoring system. Requires TS-SCM option.
  2. Installers must verify the vacuum limitation of each containment with its manufacturer prior to installation.
  3. Containments to be monitored must terminate inside the STP sump.
  4. Vacuum hose, fittings and other installation accessories are also available. Contact Franklin Fueling Systems for more details.